Code: 600-210-0AH01
Marke: Helmholz
| General information |
|---|
| Order number | 600-210-0AH01 |
|---|
| Article name | DI 8x DC 24 V |
|---|
| Scope of delivery | DI 8x DC 24 V |
|---|
| Dimensions (DxWxH) | 110 x 14 x 73 mm |
|---|
| Weight | Approx. 70 g |
|---|
| Number of inputs | 8 |
|---|
| Electrical isolation |
|---|
| from the backplane bus | Yes |
|---|
| Between the channels | No |
|---|
| Current draw |
|---|
| External | Max. 0 mA |
|---|
| Internal | Max. 22 mA |
|---|
| Power dissipation | Max. 1.85 W |
|---|
| Input characteristic curve | Type 2, EN 61131-2 |
|---|
| Reverse polarity protection for inputs | Yes |
|---|
| Input voltage |
|---|
| For signal "0” | -3 V … 9 V |
|---|
| For signal "1” | 12 V … 30 V |
|---|
| Hot-swap capable | Yes |
|---|
| Ambient conditions |
|---|
| Ambient temperature | 0 °C … +60 °C |
|---|
| Transport and storage temperature | -20 °C … +80 °C |
|---|
| Relative air humidity | 95 % r H without condensation |
|---|
| Protection rating | IP 20 |
|---|
| Certifications | CE, UL |
|---|
| UL |
|---|
| Surrounding Air Temperature | 0 °C … +60°C |
|---|
| Pollution degree | 2 |
|---|
| CE |
|---|
| Noise immunity | DIN EN 61000-6-2 “EMC Immunity” |
|---|
| Interference emission | DIN EN 61000-6-4 “EMC Emission” |
|---|
| Vibration and shock resistance | DIN EN 60068-2-6:2008 „Vibration“, DIN EN 60068-2-27:2010 „Shock" |
|---|
| RoHS | Yes |
|---|
| REACH | Yes |
|---|
Fordern Sie ein Angebot an