The SSW7-TS can be used for remote maintenance of your system over a modem connection. To this purpose, a commercially available external modem (analog, ISDN, GSM) is connected to the RS232 interface of the SSW7-TS.
For local use, just connect the RS232 interface of the SSW7-TS to your PC. It automatically recognizes the baud rate used by the PC (9.6 to 115.2 kBaud).
On the system side, you can connect the SSW7-TS to an MPI network with 187.5 or 19.2 kbps.
On the PC, the programming software and teleservice software are required (such as teleservice for Simatic* STEP* 7) to parameterize the SSW7-TS when needed or to manage the modem connections. Without modem and teleservice software, the SSW7-TS can be used locally as a SSW7.
The SSW7->TS is supplied with voltage by the MPI bus of the CPU and can be deployed at any location in the system using an optional 24 V connection.
It is also possible to load the SSW7-TS with new firmware using a modem connection, which makes it possible to realize a functional expansion of an adapter already installed in the system.
Parameterization and diagnostic functions are possible using the SHTools software.
| General information |
|---|
| Order number | 700-751-8VK21 |
|---|
| Article name | SSw-7 TS, MPI Adapter with teleservice function |
|---|
| Scope of delivery | SSW7-TS, Manual, CD with Software |
|---|
| Dimensions (DxWxH) | 105 x 53 x 29 mm |
|---|
| Weight | approx. 180 g |
|---|
| Supply voltage | 24 V DC, 18...30 V |
|---|
| Current draw maximal | 45 mA |
|---|
| MPI interface |
|---|
| Type | RS485 |
|---|
| Transmission rate | 19,2 or 187,5 kbps |
|---|
| Connection | SUB-D, 9 pin; with PG interface and terminating resistor |
|---|
| Communication interface |
|---|
| Type | RS232 |
|---|
| Transmission rate | 9,6...115,2 kbps |
|---|
| Protocol | PC <-> S7 via modem oder local |
|---|
| Connection | Connector, SUB-D, 9 pin |
|---|
| Protection rating | IP 20 |
|---|