Code: TB-I14O3 up to 990 min
Marke: Zander Aachen
TALOS® has incorporated the desired functionality in a flexible manner. The desired configuration can be selected and individual functions such as delay times can be parametrized directly on the device via the menu in an easy and quick manner. This implies: no expensive programming operations, quick and easy operation and commissioning without any other ancillary equipment such as PC. A built-in monitoring device avoids long trouble-shooting hours and downtime.
The 14 safety inputs can be variably linked, with or without time functions, with 3 safety and 6 auxiliary outputs by means of logic.
TALOS® TB-I14O3 - up to 990 min | |
---|
Safety function | Emergency stop monitoring, safety guard monitoring, light grids monitoring, for furnaces in continuous operation, stop category 0/1 |
---|
Certified according to | EN ISO 13849-1:2015, EN 50156-1:2015, EN62061:2005 + AC: 2010 + A1:2013 + A2:2015, IEC 61508 Parts 1-7:2010, IEC 61511-1:2016, EN 746-2:2010 |
---|
Approvals | CE, TUV |
---|
Supply Voltage | UB: DC 24 V (+/- 15 %) |
---|
Power consumption | 3,8 W (all inputs activated / no load operation) |
---|
Number of safe inputs | 14 safe inputs / 3 start inputs |
---|
Number of safe semiconductor outputs | 3 |
---|
Switching capability per safe output | UB / 500 mA; PNP; short circuit proof |
---|
Adjustable delay time | 0 - 990 min |
---|
Number of auxiliary semiconductor outputs | 6 |
---|
Switching capability per auxiliary output | 1 x UB / 500 mA; 5 x UB / 50 mA; PNP; short circuit proof |
---|
Number of pulsed outputs | 4 |
---|
Input voltage | DC 24 V (+/- 15 %) |
---|
PL; Cat.; SILCL (EN ISO 13849-1; IEC 62061; IEC 61508) | PL e; Cat. 4; SILCL 3 |
---|
Dimensions | 45 x 99 x 118 mm |
---|
TALOS ® TB-I14O3m incl. plug-in screw terminals | 474601 |
---|
TALOS ® TB-I14O3m incl. plug-in spring-cage terminals | 475601 |
---|
Fordern Sie ein Angebot an