Stego FPI/FPO 018 | UP TO 1010 M³/H (291 X 291 MM) Filter Fan Plus

Stego FPI/FPO 018 | UP TO 1010 M³/H (291 X 291 MM) Filter Fan Plus

Code: FPI/FPO 018 | UP TO 1010 M³/H (291 X 291 MM)
Brand: Stego
Axial fan, ball bearing

fan speed 1: service life L10 at +40 °C (+104 °F): min. 76,000 h
rotor metal
fan speed 2: service life L10 at +40 °C (+104 °F): min. 54,000 h
rotor plastic

Connection 3-pole clamp for 2.5 mm², clamping torque 0.8 Nm max.
Casing, hood, flaps plastic according to UL94 V-0, light grey;
UV light resistant according to UL746C (f1)
Enclosure cut-out 291 x 291+1 mm
Mounting frame 4 built-in ratchet braces for mounting
(6 notches for wall thickness 1-4 mm).
Additional use of screws possible if needed1.
Filter mat ISO coarse 55 % acc. to ISO 16890 (G3),
initial gravimetric arrestance 57 %
Filter material synthetic fibre with progressive construction, temperature
resistant to +100°C, self-extinguishing class F1,
moisture resistant to 100% RH, reusable
Operating temperature

fan speed 1 & 2, 50 Hz: -25 to +55 °C (-13 to +131 °F)
fan speed 1, 60 Hz: -25 to +35 °C (-13 to +95 °F)
fan speed 2, 60 Hz: -25 to +50 °C (-13 to +122 °F)

Storage temperature -40 to +70 °C (-40 to +158 °F)
Operating/Storage humidity max. 75 % RH (non-condensing)
Protection type/Protection class IP54 / I (earthed)
Environmental rating UL/NEMA UL TYPE 12 / NEMA 12
Approvals VDE, UL File No. E234324, EAC
Note other voltages on request

1 Drilling marks for screw mounting are indicated on mounting frame.

AIRFLOW DIRECTION "IN": FILTER FAN FPI 018

Art. No. Operating voltage Speed Air volume,
free flow
Air volume
with exit filter
Current
consumption
(50/60 Hz)
Power
consumption
Average noise level
(DIN EN ISO 4871)
Depth in
enclosure
Weight
(approx.)
Filter mat
01874.0-30 AC 230 V, 50/60 Hz 1 433 m³/h 373 m³/h 400/480 mA 95 W 62 dB (A) 160 mm 3.1 kg G3
01874.0-31 AC 230 V, 50/60 Hz 2 624 m³/h 560 m³/h 550/700 mA 140 W 70 dB (A) 160 mm 3.3 kg G3
01874.9-30 AC 115 V, 50/60 Hz 1 394 m³/h 339 m³/h 660/800 mA 90 W 61 dB (A) 160 mm 3.1 kg G3
01874.9-31 AC 115 V, 50/60 Hz 2 665 m³/h 593 m³/h 1100/1450 mA 165 W 72 dB (A) 160 mm 3.3 kg G3

AIRFLOW DIRECTION "IN": EXIT FILTER FPI 118

Art. No. Depth in enclosure Weight (approx.) Air outlet
11874.0-00 50 mm 1.0 kg air-flap outlet technology

AIRFLOW DIRECTION "OUT": FILTER FAN FPO 018

Art. No. Operating
voltage
Speed Air volume,
free flow
Air volume
with intake filter
Current
consumption
(50/60 Hz)
Power
consumption
Average noise level
(DIN EN ISO 4871)
Depth in
enclosure
Weight
(approx.)
Air outlet
01884.0-00 AC 230 V, 50/60 Hz 1 727 m³/h 413 m³/h 400/480 mA 95 W 63 dB (A) 160 mm 3.2 kg air-flaps
01884.0-01 AC 230 V, 50/60 Hz 2 1010 m³/h 599 m³/h 550/700 mA 140 W 70 dB (A) 160 mm 3.4 kg air-flaps
01884.9-00 AC 115 V, 50/60 Hz 1 703 m³/h 391 m³/h 660/800 mA 90 W 62 dB (A) 160 mm 3.2 kg air-flaps
01884.9-01 AC 115 V, 50/60 Hz 2 1031 m³/h 609 m³/h 1100/1450 mA 165 W 71 dB (A) 160 mm 3.4 kg air-flaps

AIRFLOW DIRECTION "OUT": INTAKE FILTER FPO 118

Art. No. Depth in enclosure Weight (approx.) Filter mat
11884.0-30 25 mm 0.8 kg ISO coarse 55 % acc. to ISO 16890 (G3), initial gravimetric arrestance 57 %

FILTER MAT FM 086

Filter class 283 x 283 mm Initial gravimetric arrestance 1 packaging unit
ISO coarse 55 % acc. to ISO 16890 (G3) Art. No. 08637.0-00 57 % 5 pieces

TECHNICAL DRAWINGS

FPI 018/FPI 118
FPO 018/FPO 118

Stego Datasheets

Country & Language File Name Download Link
United States (English) stego-EN_54310.pdf Download
Deutschland (Deutsch) stego-DE_71351.pdf Download
Italy (Italiano) stego-IT_60429.pdf Download

Request a Quote