Code: 600-254-4AB02
Brand: Helmholz
| General information |
|---|
| Order number | 600-254-4AB02 |
|---|
| Article name | AI 2x TC, Iso., 16 bit |
|---|
| Scope of delivery | AI 2x TC, Iso., 16 bit |
|---|
| Dimensions (DxWxH) | 110 x 14 x 73 mm |
|---|
| Weight | Approx. 70 g |
|---|
| Number of inputs | 2 |
|---|
| Electrical isolation |
|---|
| from the backplane bus | Yes |
|---|
| Between the channels | Yes |
|---|
| Internal | Max. 140 mA |
|---|
| Power dissipation | Max. 1 W |
|---|
| Measuring ranges | ± 80 mV |
|---|
| Thermocouples | E (-270 °C … 990 °C) J (-210 °C ... 1200 °C) K (-270 °C … 1380 °C) N (-270 °C … 1320 °C) R (-50 °C … 1775 °C) S (-50 °C … 1775 °C) T (-270 °C … 405 °C) B (0 °C … 1800 °C) C (0 °C … 2320 °C) L (0 °C … 900 °C) |
|---|
| Measuring method | Integration |
|---|
| Measurement resolution | 15 bits + sign |
|---|
| Interference frequency suppression | None | 10 Hz | 50 Hz | 60 Hz | 400 Hz |
|---|
| Refresh rate / conversion rate | Depends on the interference frequency suppression setting being used: None: 2 ms 400 Hz: 8 ms 60 Hz: 51 ms 50 Hz: 60 ms 10 Hz: 160 ms |
|---|
| Diagnoses | Upper measuring range limit exceeded (overflow), lower measuring range limit fallen below (underflow), parameter assignment error |
|---|
| Process alarms | Upper and lower limit per channel |
|---|
| Error limits |
|---|
| Operational error limit in the entire temperature range | ±0.5 % relative to the nominal range |
|---|
| Basic error limit at 25 °C | ±0.3 % relative to the nominal range |
|---|
| Temperature error | ±0.005 %/K relative to the nominal range |
|---|
| Linearity error | ±0.05 %/K relative to the nominal range |
|---|
| Repeating accuracy in steady state at 25 °C | ±0.05 %/K relative to the nominal range |
|---|
| Parameter configuration length | 26 bytes |
|---|
| General error indicator | Red LED |
|---|
| Hot-swap capable | Yes |
|---|
| Ambient conditions |
|---|
| Ambient temperature | 0 °C … +60 °C |
|---|
| Transport and storage temperature | -20 °C … +80 °C |
|---|
| Relative air humidity | 95 % r H without condensation |
|---|
| Protection rating | IP 20 |
|---|
| Certifications | CE, UL |
|---|
| UL |
|---|
| Surrounding Air Temperature | 0 °C … +60°C |
|---|
| Pollution degree | 2 |
|---|
| CE |
|---|
| Noise immunity | DIN EN 61000-6-2 “EMC Immunity” |
|---|
| Interference emission | DIN EN 61000-6-4 “EMC Emission” |
|---|
| Vibration and shock resistance | DIN EN 60068-2-6:2008 „Vibration“, DIN EN 60068-2-27:2010 „Shock" |
|---|
| RoHS | Yes |
|---|
| REACH | Yes |
|---|
Request a Quote