Código: 600-220-0DP21
Marca: Helmholz
General information |
---|
| Order number | 600-220-0DP21 |
---|
| Article name | DO 16 x DC 24 V, 300 mA, sink |
---|
| Scope of delivery | DO 16 x DC 24 V |
---|
| Dimensions (DxWxH) | 110 x 25 x 73 mm |
---|
| Weight | approx. 110 g |
---|
Number of outputs | 16 |
---|
Electrical isolation |
---|
| from the backplane bus | Ja |
---|
| Between the channels | Nein |
---|
Supply voltage UP, US |
---|
| Rated value | -24 V DC |
---|
| Ripple USS | max. 3,6 V |
---|
| Permissible range (with ripple) | 20 ... 30 V |
---|
| Voltage for t < 10 ms | 50 V |
---|
Output current |
---|
| Rated value | 300 mA |
---|
| Leakage current | max. 0,5 mA |
---|
Current draw |
---|
| External | Max. 80 mA + load |
---|
| Internal | Max. 47 mA |
---|
Power dissipation | Max. 2.5 W |
---|
Output short-circuit protection | Electronic, for each individual channel |
---|
Inductive cutoff voltage limit | -48 V |
---|
Hot-swap capable | Yes |
---|
Ambient conditions |
---|
| Ambient temperature | 0 °C … +60 °C |
---|
| Transport and storage temperature | -20 °C … +80 °C |
---|
| Relative air humidity | 95 % r H without condensation |
---|
| Protection rating | IP 20 |
---|
| Certifications | CE, UL |
---|
UL |
---|
| Surrounding Air Temperature | 0 °C … +60°C |
---|
| Pollution degree | 2 |
---|
CE |
---|
| Noise immunity | DIN EN 61000-6-2 “EMC Immunity” |
---|
| Interference emission | DIN EN 61000-6-4 “EMC Emission” |
---|
| Vibration and shock resistance | DIN EN 60068-2-8:2008 “Vibration”, DIN EN 60068-27:2010 “Shock“ |
---|
| RoHS | Yes |
---|
| REACH | Yes |
---|
Solicitar una Cotización