Código: 600-253-4BH21
Marca: Helmholz
General information |
---|
| Order number | 600-253-4BH21 |
---|
| Article name | AI 8 x R, RTD, 16 bit, 2 wire |
---|
| Scope of delivery | AI 8 x R, RTD, 16 bit, 2 wire |
---|
Number of inputs | 8 |
---|
Electrical isolation |
---|
| from the backplane bus | Yes |
---|
| Between the channels | No |
---|
Internal | Max. 140 mA |
---|
Power dissipation | Max. 1 W |
---|
Measuring ranges | 150 Ohm / 300 Ohm / 600 Ohm / 3000 Ohm / 6000 Ohm PT 100 / PT 1000 Ni 100 / Ni 1000 LGNi 1000 PT 100 Klima / PT 1000 Klima |
---|
Measuring method | Integration |
---|
Measurement resolution | 15 bits + sign |
---|
Interference frequency suppression | None | 10 Hz | 50 Hz | 60 Hz | 400 Hz |
---|
Refresh rate / conversion rate | Number of active channels x conversion time +16 ms for wire break detection for each channel when activated. The conversion time will depend on the interference frequency suppression: None: 8 ms 400 Hz: 45 ms 60 Hz: 109 ms 50 Hz: 128 ms 10 Hz: 342 ms |
---|
Diagnoses | Upper measuring range limit exceeded (overflow), lower measuring range limit fallen below (underflow), wire break, parameter assignment error |
---|
Process alarms | Upper and lower limit per channel |
---|
Error limits |
---|
| Operational error limit in the entire temperature range | ±0.5 % relative to the nominal range |
---|
| Basic error limit at 25 °C | ±0.3 % relative to the nominal range |
---|
| Temperature error | ±0.005 %/K relative to the nominal range |
---|
| Linearity error | ±0.05 %/K relative to the nominal range |
---|
| Repeating accuracy in steady state at 25 °C | ±0.05 %/K relative to the nominal range |
---|
Parameter configuration length | 10 Bytes |
---|
General error indicator | Red LED |
---|
Hot-swap capable | Yes |
---|
Ambient conditions |
---|
| Ambient temperature | 0 °C … +60 °C |
---|
| Transport and storage temperature | -20 °C … +80 °C |
---|
| Relative air humidity | 95 % r H without condensation |
---|
| Protection rating | IP 20 |
---|
| Certifications | CE, UL |
---|
UL |
---|
| Surrounding Air Temperature | 0 °C … +60°C |
---|
| Pollution degree | 2 |
---|
CE |
---|
| Noise immunity | DIN EN 61000-6-2 “EMC Immunity” |
---|
| Interference emission | DIN EN 61000-6-4 “EMC Emission” |
---|
| Vibration and shock resistance | DIN EN 60068-2-6:2008 „Vibration“, DIN EN 60068-2-27:2010 „Shock" |
---|
| RoHS | Yes |
---|
| REACH | Yes |
---|
Solicitar una Cotización