Stego FPI/FPO 018 | UP TO 263 M³/H (176 X 176 MM) Filter Fan Plus

Stego FPI/FPO 018 | UP TO 263 M³/H (176 X 176 MM) Filter Fan Plus

Code: FPI/FPO 018 | UP TO 263 M³/H (176 X 176 MM)
Marque: Stego
Axial fan, ball bearingservice life L10 at +40 °C (+104 °F): min. 65,000 h
fan body aluminium, rotor metal
Connection3-pole clamp for 2.5 mm², clamping torque 0.8 Nm max.
Casing, hood, flapsplastic according to UL94 V-0, light grey;
UV light resistant according to UL746C (f1)
Enclosure cut-out176 x 176+1 mm
Mounting frame4 built-in ratchet braces for mounting
(6 notches for wall thickness 1-4 mm).
Additional use of screws possible if needed1.
Filter matISO coarse 55 % acc. to ISO 16890 (G3),
initial gravimetric arrestance 57 %
Filter materialsynthetic fibre with progressive construction, temperature
resistant to +100°C, self-extinguishing class F1,
moisture resistant to 100% RH, reusable
Operating temperature50 Hz: -25 to +50 °C (-13 to +122 °F)
60 Hz: -25 to +70 °C (-13 to +158 °F)
Storage temperature-40 to +70 °C (-40 to +158 °F)
Operating/Storage humiditymax. 90 % RH (non-condensing)
Protection type/Protection classIP54 / I (earthed)
Environmental rating UL/NEMA UL TYPE 12 / NEMA 12
ApprovalsVDE, UL File No. E234324, EAC
Noteother voltages on request

1 Drilling marks for screw mounting are indicated on mounting frame.

AIRFLOW DIRECTION "IN": FILTER FAN FPI 018

Art. No.Operating voltageAir volume,
free flow
Air volume
with exit filter
Current
consumption
(50/60 Hz)
Power
consumption
Average noise level
(DIN EN ISO 4871)
Depth in
enclosure
Weight
(approx.)
Filter mat
01872.0-30AC 230 V, 50/60 Hz170 m³/h139 m³/h310/250 mA45 W55 dB (A)117 mm1.6 kgG3
01872.9-30AC 115 V, 50/60 Hz204 m³/h187 m³/h560/470 mA38 W58 dB (A)117 mm1.6 kgG3

AIRFLOW DIRECTION "IN": EXIT FILTER FPI 118

Art. No.Depth in enclosureWeight (approx.)Air outlet
11872.0-0043 mm0.4 kgair-flap outlet technology

AIRFLOW DIRECTION "OUT": FILTER FAN FPO 018

Art. No.Operating
voltage
Air volume,
free flow
Air volume
with intake filter
Current
consumption
(50/60 Hz)
Power
consumption
Average noise level
(DIN EN ISO 4871)
Depth in
enclosure
Weight
(approx.)
Air outlet
01882.0-00AC 230 V, 50/60 Hz263 m³/h137 m³/h310/250 mA45 W56 dB (A)117 mm1.6 kgair-flaps
01882.9-00AC 115 V, 50/60 Hz313 m³/h166 m³/h560/470 mA38 W60 dB (A)117 mm1.6 kgair-flaps

AIRFLOW DIRECTION "OUT": INTAKE FILTER FPO 118

Art. No.Depth in enclosureWeight (approx.)Filter mat
11882.0-3025 mm0.4 kgISO coarse 55 % acc. to ISO 16890 (G3), initial gravimetric arrestance 57 %

FILTER MAT FM 086

Filter class168 x 168 mmInitial gravimetric arrestance1 packing unit
ISO coarse 55 % acc. to ISO 16890 (G3)Art. No. 08635.0-0057 %5 pieces

TECHNICAL DRAWINGS

FPI 018/FPI 118
FPO 018/FPO 11

Stego Fiches techniques

Pays et langue Nom du fichier Lien de téléchargement
United States (English) stego-EN_54310.pdf Télécharger
Deutschland (Deutsch) stego-DE_71351.pdf Télécharger
Italy (Italiano) stego-IT_60429.pdf Télécharger

Demande de devis