Codice: 600-260-4AD01
Marchio: Helmholz
General information |
---|
| Order number | 600-260-4AD01 |
---|
| Article name | AO 4x I, 0/4 ... 20 mA, 12 bit |
---|
| Scope of delivery | AO 4x I, 0/4 ... 20 mA, 12 bit |
---|
| Dimensions (DxWxH) | 110 x 14 x 73 mm |
---|
| Weight | Approx. 70 g |
---|
Number of outputs | 4 |
---|
Output ranges | 0 … 20 mA, 4 … 20 mA |
---|
Electrical isolation |
---|
| from the backplane bus | Yes |
---|
| Between the channels | No |
---|
Current draw |
---|
| External | Max. 100 mA |
---|
| Internal | Max. 26 mA |
---|
Power dissipation | Max. 3 W |
---|
Connection for actuators | 2-wire connection |
---|
Load resistance | Max. 600 ohms |
---|
Inductive load | Max. 100 mH |
---|
No-load voltage | max. 18 V |
---|
Measurement resolution | 12 bit |
---|
Values presentation | SIMATIC* S7 | SIMATIC* S5 | INT16 |
---|
Refresh time | 0.2 ms |
---|
Settling time | 0.2 ms for resistive loads, 2.2 ms for capacitive loads, 0.5 ms for inductive loads (<=1 mH), 3.3 ms for inductive loads (<=3.3 mH) |
---|
Diagnoses | External reference voltage missing (L+), wire break, parameter assignment error |
---|
Process alarms | Upper and lower limit per channel |
---|
Error limits |
---|
| Operational error limit in the entire temperature range | ±0.5 % relative to the nominal range |
---|
| Basic error limit at 25 °C | ±0.3 % relative to the nominal range |
---|
| Temperature error | ±0.005 %/K relative to the nominal range |
---|
| Linearity error | ±0.05 %/K relative to the nominal range |
---|
| Repeating accuracy in steady state at 25 °C | ±0.05 %/K relative to the nominal range |
---|
Parameter configuration length | 13 bytes |
---|
General error indicator | Red LED |
---|
Hot-swap capable | Yes |
---|
Ambient conditions |
---|
| Ambient temperature | 0 °C … +60 °C |
---|
| Transport and storage temperature | -20 °C … +80 °C |
---|
| Relative air humidity | 95 % r H without condensation |
---|
| Protection rating | IP 20 |
---|
| Certifications | CE, UL |
---|
UL |
---|
| Surrounding Air Temperature | 0 °C … +60°C |
---|
| Pollution degree | 2 |
---|
CE |
---|
| Noise immunity | DIN EN 61000-6-2 “EMC Immunity” |
---|
| Interference emission | DIN EN 61000-6-4 “EMC Emission” |
---|
| Vibration and shock resistance | DIN EN 60068-2-6:2008 „Vibration“, DIN EN 60068-2-27:2010 „Shock" |
---|
| RoHS | Yes |
---|
| REACH | Yes |
---|