Kod: SCB-02
Marka: Zander Aachen
SCB-02 |
|
Safety function |
Emergency stop monitoring, safety guard monitoring, light grids monitoring, furnaces in continuous operation, stop category 0/1 |
Certified according to |
EN ISO 13849-1:2015, EN 50156-1:2015, EN62061:2005 + AC: 2010 + A1:2013 + A2:2015, IEC 61508 Parts 1-7:2010, IEC 61511-1:2016, EN 746-2:2010 |
Approvals |
CE, TUV |
Supply voltage |
UB: DC 24 V (+ 10 /- 15 %) |
Number of safe outputs |
2 |
Switching capability per safe relay outputs |
AC -15: 3 A / 250 V; DC -13: 2 A / 24 V |
Switching capability for safe semiconductor outputs |
UB / 500 mA; PNP; short circuit proof |
Number of auxiliary semiconductor outputs |
0 |
Switching capability for auxiliary outputs |
C1: UB / 500 mA; PNP; short circuit proof C2: UB / 50 mA; PNP; short circuit proof |
Number of non time-delayed outputs |
2 (depending on configuration Pr 00 - Pr 02) |
Number of time-delayed outputs |
2 (depending on configuration Pr 00 - Pr 02) |
Adjustable delay |
0 - 99 s (SCB-02) 0 - 99 min (SCB-02m) 0 - 99 h (SCB-02h) |
Number of safe inputs |
1 x 2 channel |
Starting behavior |
Automatic start or manual, monitored start |
PL; Cat.; SILCL (EN ISO 13849-1; EN/IEC 62061) |
PL e; Cat. 4; SILCL 3 |
Dimensions |
22.5 x 99 x 118 mm |
SCB with plug-in screw terminals |
|
Order No. SCB-02 / SCB-02-01, 2 relay contacts, 0 - 99 s |
474490 / 474495 inverted switching auxiliary outputs |
Order No. SCB-02 / SCB-02-01, 2 relay contacts, 0 - 99 m |
474491 / 474496 inverted switching auxiliary outputs |
Order No. SCB-02 / SCB-02-01, 2 relay contacts, 0 - 99 h |
474492 / 474497 inverted switching auxiliary outputs |
SCB with push-in spring connection |
|
Order No. SCB-02 / SCB-02-01, 2 relay contacts, 0 - 99 s |
475490 / 475495 inverted switching auxiliary outputs |
Order No. SCB-02 / SCB-02-01, 2 relay contacts, 0 - 99 m |
475491 / 475496 inverted switching auxiliary outputs |
Order No. SCB-02 / SCB-02-01, 2 relay contacts, 0 - 99 h |
475492 / 475497 inverted switching auxiliary outputs |